Technical data
Current rating range:5~30A
Input voltage rating:125/250VAC; 32/50VDC
Interrupting Capacity : 125/250VAC x 1,000A(UL 1077)
Typical life :1,000 operations at 200% overload1,000 operations at 200% overload
Insulation co-ordination:Rated impulse withstand voltage 2.5kV Rated impulse withstand voltage 2.5kV Dielectric Strength:>
1.500VAC/min.
Insulation Resistance:>100MOHM (DC 500V)
Degree of protection:Terminal area IP00, operating area IP40
Mechanical/Environmental Data
Operating Ambient Temperature: -10℃ to +60℃
Mounting: Various options. See Ordering Information and drawings
Termination: 250''(6.35mm)quick connects or solder terminals
Calibration(at25℃)
100% of Rated Current: Hold , No Trip 300% of Rated Current: 1.5-5.0 sec Trip •
200% of Rated Current: 5-30 sec Trip •
150% ofRated Current: Trip Within 1 Hour
Approval
Approval & File No. Rated current Rated voltage
CUL UL E155159 3-50A 125/250VAC; 50VDC
TUV SUD B15 09 58611 007 3-30A 125/250VAC; 32VDC
CCC 201101030752058 3-30A 125/250VAC.
VDE 40036160 3-16A 125/250VAC
CSA 102199 3-30A 125VAC
Typical applicationsTypical applications
Tarnsforms, Motors, Battery chargers, Power supplies
appliances, extra low voltage systems, machineryappliances, extra low voltage systems, machinery