CP30-BA 2p 1-M 0.5 a.CP30-BA 2p 1-M 1ACP30-BA 2p 1-M 2ACP30-BA 2p 1-M 3ACP30-BA 2p 1-M 5ACP30-BA 2p 1-M 7ACP30-BA 2p 1-M 10ACP30-BA 2p 1-M 15ACP30-BA 2p 1-M 20ACP30-BA 2p 1-M 30A (take-out CDN)Performance specifications
Type | サーキットプロテクタ | ||
Series name | CP series | ||
Frame A | 30 | ||
Model | CP30-BA 2p 1-M | ||
Number of Poles | 2 | ||
Rated current (A) | 0.5 1 2 3 5 7 10 15 20 30 | ||
Rated insulation voltage (V) | 250 | ||
Rated short circuit breaking capacities (kA) | UL 1077CSA C22.2 No.235 | Rated voltage (AC) | 250 |
Rated voltage (DC) | 125 | ||
AC250V | 2.5 kA | ||
DC125V | 2.5 kA | ||
IEC 60934EN 60934GB 17701 (Icn) | AC230V | 2.5 kA | |
DC120V | 2.5 kA | ||
JIS C 4610 (Icn) | AC230V | 2.5 kA | |
DC120V | 2.5 kA | ||
IEC 60947-2EN 60947-2JIS C 8201-2-1 Ann.1(Icu/Ics) | AC230V | 2.5/2.5kA | |
DC120V | 2.5/2.5kA | ||
Rated impulse withstand voltage (kV) | 2.5 | ||
Type of current | AC/DC | ||
Reverse connection | -Friendly | ||
Life (times) | Mechanical | 10000 | |
Electrical | 6000 | ||
Reference ambient temperature | 40 (T40) | ||
Internal circuit | Connected in series | ||
Operating characteristics | Medium-speed type | ||
Pull-off | Medium-speed type | ||
Connection method | Screw terminals | ||
Operation scheme | S-type (IEC 60934) | ||
Remove the freedom pull / operating system | Remove the pull freedom Trip-free (IEC 60934) | ||
External dimensions (mm) | a | 35 | |
b | 73 | ||
c | 65 | ||
CA | 65 | ||
Product weight (kg) | 0.16 | ||
Body mounting method | Surface mountingIEC 35 mm rail mountingMounting bracket | ||
Optional parts | Terminal cover | ◎ | |
Embedded embedded hardware (FP) | ◎ | ||
Back wire terminal (BT) | ◎ | ||
Comes with Terminal cover (TC) | ◎ | ||
Standard authentication | CURUS | Get | |
Electrical appliance safety law | Fit | ||
CCC | Get | ||
CE mark | EN 60934: TUV certificationEN 60947-2: self declaration | ||
Classification society certifications | NK Gets |